Networking Parameters (NB-IoT / LoRaWAN)
NameName#LoRaWAN-RemoteConfiguration | Description | Default Value | Value Description & Examples |
---|---|---|---|
WAN | Radio technology used for connection to backend | lte |
|
Host | Hostname / IP of the Lobaro Platform API Not used for LoRaWAN uplink | 94.130.20.37 | 94.130.20.37 = platform.lobaro.com |
Port | Port number of the Lobaro Platform API Not used for LoRaWAN uplink | 5683 |
...
MbCmd
defines, what Modbus commands are executed on the Bus, when, and what Modbus Configuration to use for them. The configuration is very flexible and allows complex setups, that include executing different commands at individual intervals or times or using multiple different Modbus parameters to address incompatible Slaves on the same installation. Any Modbus command can be sent, including writing registers or diagnostic messages.
The command is entered in Hex and without any check sums and is 6 bytes long (12 hexdigits). The default value is 010300000003
, it consists of 4 parts: 01
, 03
, 0000
, 0003
01
Address of the Slave Device. 1 byte: often 01 new devices
03
What kind of Modbus Register to read. 1 byte. 03 stand for Holding Register.
0000
Number/address of the first register to read. 2 bytes. Many devices have some value to read out at 0000.
0003
Number of consecutive registers to read from the first register. 2 bytes. This would read the registers #0, #1, and #2 in one command.
The default value of 0 0/5 * * * *:R,9600,8N1:010300000003
shows a very basic example with a single entry executed every 5 minutes using Modbus RTU to read 3 consecutive holding registers from a single slave device.
...